NeoTec Slave function module 1:
RS232 (integration of another measuring device, e.g. Testomat EVO / LAB)
|
NeoTec Slave function module 2:
4-20mA module (6x input + 4x output)
|
NeoTec Slave function module 3:
Relay module (4 relays 240 VAC)
|
Number of parameters to be measured, up to:
4
Our 4- or 8- channel system allows the processing of up to four or eight measurement signals. For this purpose, 4-20 mA/ RS232 as well as Modbus RTU are available as signal inputs. Based on the received data a visualization as well as a trend display takes place. Through modular addition of optional modules (slaves) the realization of popular control concepts is possible.Advantages:Simple operation
Integration of the Testomat® device world
Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housingModular function range expandable by NeoTec slave modules (measure, control, control)Available as installation variant or structure variant
NeoTec Select Optical Oxygen Sensor with Modbus OutputDurable and reliableStainless steel SS316- housing option for fresh waterTitanium- housing option for salt waterOptical technology allows maintenance-free use for up to 2 years Save time during set-upNo calibration required
Plug and play Digital communication Open protocol Modbus RS485 signal
NeoTec Select Optical Oxygen Sensor with Modbus OutputDurable and reliableStainless steel SS316- housing option for fresh waterTitanium- housing option for salt waterOptical technology allows maintenance-free use for up to 2 years Save time during set-upNo calibration required
Plug and play Digital communication Open protocol Modbus RS485 signal
Head transmitter:
4-20 mA
|
Tee:
1.5" flow cell with 1" inner thread NPT
|
measuring range:
0.1-1.000 μS/cm
The conductivity measuring package consists of a 3 meter connection cable, a 4-20mA head transmitter, and the conductivity sensor. Due to the design of the sensor assembly, only the sensor needs to be replaced, when it should be worn out . All other components of this system can be used continuously. For an optimal process integration the NeoTec sensor is delivered with a fitting T-piece.
Advantages:
preconfigured for NeoTecMaster®
modular design
industry standard
resource friendly
Head transmitter:
Modbus 12-24 VDC
|
Tee:
1.5" flow cell with 1" inner thread NPT
|
measuring range:
0.1-500 μS/cm
The conductivity sensor consists of a 3 meter connection cable, a Modbus head transmitter, and the conductivity sensor. Due to the design of the sensor assembly, only the sensor needs to be replaced. All other components of this system can be used continuously. For an optimal process integration the NeoTec sensor is delivered with a fitting T-piece.
Advantages:Preconfigured for NeoTecMaster®
Modular design
Industry standard
conserves resources
The modular pH measuring package consists of a 3 m connection cable, a Modbus head transmitter, the sensor holder and the flat-head pH electrode. Due to the design of the sensor assembly, only the pH electrode needs to be replaced. All other components of this system can be used continuously. For optimal process integration, the NeoTec Sensor is supplied with a suitable T-piece.Advantages:preconfigured for NeoTecMaster®
modular design
industry standard
resource friendly
Which sensor is used?:
Conductivity cell constant c = 1
Module for manufacturer-independent integration of pH, ORP and conductivity standard sensors (PT1000 based), which do not have an integrated signal converter on site. Integration of existing/existing sensors into the NeoTecMaster® concept via 4-20 mA signal.Advantages:accommodates all pH, ORP and conductivity standard electrodes industry standard
allows the use of existing sensors
Which sensor is used?:
Conductivity cell constant c = 0.1
Module for manufacturer-independent integration of pH, ORP and conductivity standard sensors (PT1000 based), which do not have an integrated signal converter on site. Integration of existing/existing sensors into the NeoTecMaster® concept via 4-20 mA signal.Advantages:accommodates all pH, ORP and conductivity standard electrodes easy wall installationindustry standard
allows the use of existing sensors
Which sensor is used?:
Conductivity cell constant c = 1
Module for manufacturer-independent integration of pH, ORP and conductivity standard sensors (PT1000 based), which do not have an integrated signal converter on site. Integration of existing/existing sensors into the NeoTecMaster® concept via 4-20 mA signal.Advantages:accommodates all pH, ORP and conductivity standard electrodes easy wall installationindustry standard
allows the use of existing sensors
Module for manufacturer-independent integration of pH, ORP and conductivity standard sensors (PT1000 based), which do not have an integrated signal converter on site. Integration of existing/existing sensors into the NeoTecMaster® concept via 4-20 mA signal.Advantages:accommodates all pH, ORP and conductivity standard electrodes easy wall installationindustry standard
allows the use of existing sensors
The use of the NeoTec Slave 4-20 mA allows to process up to eight external 4-20 mA measuring
signals. Advantages:inversion of the input signals on the assigned outputs possible
(e.g. for concentration-dependent pump control) compact design for top hat rail mounting when using several modules, only one power supply is necessary addition of a further module for application integration possible
By using these NeoTec Slave relay modules, potential-free relay contacts are added to the overall system. All relay contacts can be freely assigned to the incoming measuring signals and can therefore be used, for example, for limit value-related control concepts or measured value-related messages.Advantages:individual implementation of:
alarm message based on received measured values and/or status messages
switching contacts for simple valve control
compact design for top hat rail mounting
when using several modules only one power supply is necessary
modular expandable according to process requirements
Our 4- or 8- channel system allows the processing of up to four or eight measurement signals. For this purpose, 4-20 mA/ RS232 as well as Modbus RTU are available as signal inputs. Based on the received data a visualization as well as a trend display takes place. Through modular addition of optional modules (slaves) the realization of popular control concepts is possible.Advantages:Simple operation
Integration of the Testomat® device world
Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housingModular function range expandable by NeoTec slave modules (measure, control, control)Available as installation variant or structure variant
Contents:
NeoTecMaster® 5 inch - 4 channel systemNeoTec Slave 4-20mA module (inputs: 8x 20mA)NeoTecMaster® IP66 housing for 5" display, light grey with front foilUSB stick for NeoTecMaster® 8GInstallation of NeoTecMaster® in housing incl. parameterisation and cabling of the NeoTecMaster®Universal power supply 24V/6A DC (100-240V AC) (144 Watt)
Our 4- or 8- channel system allows the processing of up to four or eight measurement signals. For this purpose, 4-20 mA/ RS232 as well as Modbus RTU are available as signal inputs. Based on the received data a visualization as well as a trend display takes place. Through modular addition of optional modules (slaves) the realization of popular control concepts is possible.Advantages:Simple operation
Integration of the Testomat® device world
Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housingModular function range expandable by NeoTec slave modules (measure, control, control)Available as installation variant or structure variant
Cell constant:
1
|
Maximum temperature and pressure:
max. 100 °C / max. 13 bar (200 psig)
|
Measuring resistor (temperature sensor):
PT1000
|
Version:
1/2“ NPT
Our Neomeris Select high temperature conductivity cells are suitable in a wide range of high performance applications with high temperatures and pressures.To meet these demanding technical requirements, our sensors are manufactured from 316 stainless steel with PEEK elements and feature a one-piece cell design suitable for high pressure conditions. The conductivity cells are available with different cell constants (0.1/cm and 1.0/cm) and temperature sensors (PT100 and PT1000) and are designed for a specific pressure-temperature range. Certain model types also allow you to choose between a short and long thread, depending on the installation situation.Our 1/2" inch Select LF stainless steel conductivity cell is a general purpose sensor that can be used in a variety of standard applications such as in cooling towers or water treatment plants, etc. and is easy to install. In contrast, our Select HTLF Ultra high performance conductivity cell is the top of the range model. This conductivity sensor is specially designed for boiler applications where it is permanently integrated in the boiler. Via our selection menu you can easily choose the right conductivity sensor for your application. Please contact us if you have any questions.
Cell constant:
0.1
|
Maximum temperature and pressure:
max. 200 °C / max. 17 bar (250 psig)
|
Measuring resistor (temperature sensor):
PT1000
|
Version:
3/4“ NPT for installation in 3/4“ T-piece
Our Neomeris Select high temperature conductivity cells are suitable in a wide range of high performance applications with high temperatures and pressures.To meet these demanding technical requirements, our sensors are manufactured from 316 stainless steel with PEEK elements and feature a one-piece cell design suitable for high pressure conditions. The conductivity cells are available with different cell constants (0.1/cm and 1.0/cm) and temperature sensors (PT100 and PT1000) and are designed for a specific pressure-temperature range. Certain model types also allow you to choose between a short and long thread, depending on the installation situation.Our 1/2" inch Select LF stainless steel conductivity cell is a general purpose sensor that can be used in a variety of standard applications such as in cooling towers or water treatment plants, etc. and is easy to install. In contrast, our Select HTLF Ultra high performance conductivity cell is the top of the range model. This conductivity sensor is specially designed for boiler applications where it is permanently integrated in the boiler. Via our selection menu you can easily choose the right conductivity sensor for your application. Please contact us if you have any questions.
Cell constant:
1
|
Maximum temperature and pressure:
max. 252 °C / max. 41 bar (600 psi)
|
Measuring resistor (temperature sensor):
PT100
|
Version:
3/4“ NPT for installation in 3/4“ T-piece
Our Neomeris Select high temperature conductivity cells are suitable in a wide range of high performance applications with high temperatures and pressures.To meet these demanding technical requirements, our sensors are manufactured from 316 stainless steel with PEEK elements and feature a one-piece cell design suitable for high pressure conditions. The conductivity cells are available with different cell constants (0.1/cm and 1.0/cm) and temperature sensors (PT100 and PT1000) and are designed for a specific pressure-temperature range. Certain model types also allow you to choose between a short and long thread, depending on the installation situation.Our 1/2" inch Select LF stainless steel conductivity cell is a general purpose sensor that can be used in a variety of standard applications such as in cooling towers or water treatment plants, etc. and is easy to install. In contrast, our Select HTLF Ultra high performance conductivity cell is the top of the range model. This conductivity sensor is specially designed for boiler applications where it is permanently integrated in the boiler. Via our selection menu you can easily choose the right conductivity sensor for your application. Please contact us if you have any questions.
The Testomat® 808 is a compact analyzer for the online measurement of water hardness according to the principle of " limit value monitoring by color change ". The Testomat® style="letter-spacing: 0px;"> 808 is a combination of the latest technologies based upon decades of international Testomat® experience.Applications of continuous residual hardness monitoring are for example:
Reverse osmosis plants
Boiler feed water supply
Soft water for commercial puposes
Pure water systems
Performance profile:Limit value indication (not exceeded or exceeded: green / red LED)
Modern indicator pump system
Automatic measuring process with low water consumption
Direct error and indicator quantity indication
Internal and external flushing of the measuring chamber by manual control
Control of an external rinsing valve
Three potential-free relays for:
External rinsing valve control
Limit value evaluation
External control and / or alarm processing
Safety check for 72 hours operation without supervision
Indicator quantities: 100 and 500 ml bottles
4 - 20 mA interface for defined status and error messages
RS 232 interface for firmware updates
The Testomat® 808 SIO02 is a device that was developed for measuring and monitoring deionised water (fully demineralised water) in medical facilities.
The central importance of silicate monitoring
Silicate measurement using the Testomat® 808 SIO02 is an essential aspect of compliance with a defined limit value. Precise silicate monitoring is particularly important in process water treatment in hospitals in order to prevent deposits on devices and medical devices (MD) and to ensure the effectiveness of the water treatment systems. You can choose between 10 limit values in the range from 0.3 to 1.2 ppm. By regularly monitoring the silicate content and compliance with the limit values, potential problems can be identified at an early stage and suitable measures can be taken to optimise water treatment.
The Testomat® 808 is a compact analyser for online measurement of water hardness according to the principle of "limit value monitoring with colour change" in the measuring range 0.02 - 5 ° dH (0.4 - 89 ppm). Applications of the continuous residual hardness monitoring are e.g.: Reverse osmosis systems, boiler feed water supply Soft water for commercial purposes, ultrapure water systems.
In view of the fact that the Testomat® 808 is suitable for use in multi-parameter systems due to its 4-20mA signal output, we hereby offer you the Testomat® 808 in conjunction with the NeoTecMaster® Multicontroller, which was specially developed by our company, as a package solution at a preferential price.
The 4-channel NeoTecMaster® Multicontroller included in this package enables the processing of up to four measurement signals. Via the 4-20mA NeoTec slave input module connected to the NeoTecMaster®, the data is transmitted to the NeoTecMaster® and used to display the measured value, the trend and the status messages on the 5-inch screen. In addition, the NeoTecMaster® has an RS232 interface as well as a Modbus RTU input, which you can use freely after brief technical consultation with us. (Pre-check whether your existing measurement technology to be integrated requires adjustments).
The NeoTecMaster® can be systematically supplemented with further optional NeoTec modules (function / signal converter modules) as required. This allows the future realisation of further control concepts in a flexible way.
Two modules which fundamentally extend the range of functions and are already included in the scope of delivery are our NeoTec slave relay module and the 4x 4-20mA input module. This allows you to add potential-free relay contacts to the overall system and to integrate and visualise further system technology such as sensors via the 4x 4-20mA input module. You can freely assign the relay contacts to the incoming measurement signals and thus, for example, implement simple limit value-related control concepts as well as output measurement value-related messages.
Further advantages of the NeoTecMaster:
Simple operation Integration of the Testomat® device world, here in connection with the Testomat® 808
Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® enclosure
Modular range of functions can be extended by NeoTec slave and signal converter modules (measurement, control, regulation)
Available as built-in or surface-mounted variant
Structured continuous data recording on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format
In addition, there are the proven functionalities of the Testomat® 808:
Indication of limit value undershoot or overshoot: green / red LED
Modern indicator pump system
Automatic measuring sequence with low water consumption
Direct error and indicator quantity display
Internal and external flushing of the measuring chamber by manual control
Control of an external flush valve
Three potential-free relays for: External flush valve control Limit value evaluation External control and / or alarm processing
Safety check for 72-hour operation without supervision
Indicator quantities: 100 and 500 ml bottles
4 - 20 mA interface for defined status and error messages
RS 232 interface for firmware updates
General information
Water connection and operating pressure: Depending on unit version: 0.3 - 1 bar / 0.3 x 105 to 4 x 105 Pa 1 - 4 bar / 1 x 105 to 4 x 105 Pa (from 4 to 8 bar, a pressure reducer must be used (special accessory))
Water inlet: opaque hose with 6 mm outer diameter/4 mm inner diameter
Water outlet: hose with 6 mm outer diameter/4 mm inner diameter
Water temperature: 10 to 40 °C
From 4 bar, a separately available pressure reducer must be used. Please use only the indicators approved for Testomat® 808!
Optional accessories:
NeoTecMaster unit hood
The Testomat® ECO / EVO automatically determines the water hardness by means of titration. The device is suitable for controlling the water quality of water treatment plants, drinking water systems, industrial boilers and for monitoring process water. Approved for boiler houses | component identification no.: TÜV. WÜH. 21-025 | VdTÜV bulletin water monitoring device 100 and UL-TÜV certified (only version with wide-range power supply unit).The Testomat® style="letter-spacing: 0px;"> EVO TH convinces with new functionalities:Optical water detection when filling the measuring chamber
BOB operation (operation without constant supervision)Import and export of settings (basic programming) with selectable file nameLogging of measurement data and messages / alarms using an integrated SD or optional SDHC card (2GByte)
Firmware update via SD card
LCD graphic display
Multilingual menu with easy switching (internal programming is retained)
Integrated self-test with continuous monitoring
External clear / acknowledge input
Free programmable password
Automatic bleeding of the indicator line
Doors can be changed individually
Range monitoring (fall below limit value1 / exceed limit value 2)
Permitted number of lack of water, freely programmable (for systems with temporarily low water pressure)[#mspacer#]Performance profile:High-precision titration using a piston dosing pump
Analogue output 0/4 - 20 mA
Serial RS232 interface for transfer of measurement data and messages/alarmsProgrammable hardness unit in ° dH, ° f, ppm CaCO3, mmol / l
2 independent limits with adjustable switching functions as well as switching option in accordance with an adjustable number of negativeanalyzes
Analysis initiation:
automatic interval operation (0-99 minutes)
depending on quantity via contact water meter
Indicator quantities: 100 und 500 ml bottles
The Testomat® EVO TH is supplied without a power switch. This is done to comply with the DIN EN 61010-1 safety standard for measuring, control and laboratory equipment. Of course, an external mains switch will be made available to you as a customer for purchase. You can order this from us as a disconnector under article no. 850925, "external cam switch with protection class IP65".
The Testomat® EVO TH automatically determines the water hardness by means of titration. The device is suitable for controlling the water quality of water treatment plants, drinking water systems, industrial boilers and for monitoring process water. On top of that our Testomat® EVO TH is approved for boiler houses | component identification no.: TÜV. WÜH. 21-025 | VdTÜV bulletin water monitoring device 100 and UL-TÜV certified.
It is supplemented by the Testomat® LAB CL, a robust wet chemical online measuring converter to measure the concentration of total chlorine or free chlorine in the measuring range 0 - 5 mg/l. The instrument is suitable for controlling the water quality of water treatment plants, drinking water plants, process water monitoring and for monitoring the chlorine concentration in the cooling tower process. Instrument operation is based on the DPD method according to EN ISO 7393-2. The analysis is carried out through the addition of two reagents and the measurement result is obtained after a reaction time of approx. 60 seconds (pure measurement time without flush time).
In view of the fact that the Testomat® LAB CL was developed for use in multi-parameter systems or for connection to a higher-level control system, we hereby offer you the Testomat® EVO TH and the Testomat® LAB CL in combination with the NeoTecMaster®, which was specially developed by our company, as a package solution at a preferential price.
The 4-channel NeoTecMaster® multi-parameter controller included in this package enables the processing of up to four measurement signals in this version. A signal input on the NeoTecMaster® , in this case the RS232 interface and one additional RS232 interface on the included NeoTec Slave module , are used by Testomat® EVO TH and Testomat® LAB CL to display the measured value, the trend and the status messages on the 5 inch screen. In addition to the on board RS232 interface, the NeoTecMaster® also has a Modbus RTU input, which you can use freely after brief technical consultation with us. (Pre-check whether your existing measurement technology to be integrated requires adjustments).
The NeoTecMaster® can be systematically supplemented with further optional NeoTec modules (function / signal converter modules) as required, thus enabling the future realisation of further control concepts in a flexible manner. A module that fundamentally expands the range of functions and is already included in the scope of delivery is our NeoTec slave relay module with which you can add potential-free relay contacts to the overall system. You can freely assign these to the incoming measurement signals and thus, for example, implement limit value-related control concepts, as well as output measurement-related messages.
Further advantages of the NeoTecMaster:
Simple operation
Integration of the Testomat® world of instruments, here in conjunction with the Testomat® EVO TH and Testomat® LAB CL
Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housing
Modular range of functions can be extended by NeoTec slave and signal converter modules (measurement, control, regulation)
Available as built-in or surface-mounted variant Structured continuous data recording on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format
In addition, there are proven Testomat® functionalities of both devices:
Optimised water detection based on an optical measuring method
RS232 interface for transmission of measured values and error messages
Import and export of settings (basic programming)
Logging of measurement data and messages/alarms via integrated SD card or optionally usable SDHC card (2GByte)
Firmware update via SD card
Integrated self-test with continuous monitoring
Automatic venting of the indicator line
Performance profil Testomat® EVO TH:
High-precision titration by means of piston metering pump
LCD graphic display
Multilingual menu with easy switching (internal programming is retained)
External clear / acknowledge input
Free programmable password
Range monitoring (fall below limit value1 / exceed limit value 2)
Permitted number of lack of water, freely programmable (for systems with temporarily low water pressure)
Reliable and low-maintenance operation
Minimal indicator and water consumption
Analogue output 4 - 20 mA for transmission of measured values
Programmable hardness unit in °dH, °f, ppm CaCO3, mmol/l
Collective alarm output
Indicator quantities: 100 and 500 ml bottles
Analysis trigger:
automatic interval operation (0-99 minutes)
depending on quantity via contact water meter
Performance profil Testomat® LAB CL:
High-precision peristaltic pumps
Reliable and low-maintenance operation
Minimal reagent and water consumption
Analog output 4 - 20 mA for transmission of measured values
RS232 interface for transmission of measured values & fault messages
Execution of parameterisation by means of SD card or "Service Monitor" software via mini-USB (on the unit side) to USB 2.0 (e.g. PC/notebook)
Multilingual software menu in German, English, French, Dutch, Portoguese
Compact design
Common alarm output
Optimised reagents: Only 2 reagents for the determination of total chlorine
Optimised reagent set: filling quantities are coordinated so that the reagent set is used up almost evenly
Analysis triggering:
Automatic interval operation (interval pause adjustable from 10-60 minutes)
Measuring phase mode (start impulse triggers a sequence of analyses for a period of 10 minutes to 12 hours)
External analysis input (start/stop)
Hand start
Optional accessories available:
OLED display for Testomat® LAB
Protective cover to increase the IP protection class of the Testomat® LAB
NeoTecMaster instrument cover
The Testomat® EVO TH CAL with additional calibration function automatically determines the water hardness by means of titration. The device is suitable for controlling the water quality of water treatment, drinking water systems, industrial boilers and for monitoring process water.The Testomat® EVO TH CAL corresponds in function to the Testomat® EVO TH:Optical water detection when filling the measuring chamberImport and export of settings (basic programming) with selectable file nameLogging of measurement data and messages / alarms using an integrated SD or optional SDHC card (2GByte)Firmware update via SD cardLCD graphic displayMultilingual menu with easy switching (internal programming is retained)Integrated self-test with continuous monitoringExternal clear / acknowledge inputFree programmable passwordAutomatic bleeding of the indicator lineDoors can be changed individuallyRange monitoring (fall below limit value1 / exceed limit value 2)Permitted number of lack of water, freely programmable (for systems with temporarily low water pressure)[#mspacer#] Performance profile:
High-precision titration using a piston dosing pumpAnalogue output 0/4 - 20 mASerial RS232 interface for transfer of measurement data and messages/alarmsProgrammable hardness unit in ° dH, ° f, ppm CaCO3, mmol / l2 independent limits with adjustable switching functions as well as switching option in accordance with an adjustable number of negative
analyzes Analysis initiation:automatic interval operation (0-99 minutes)depending on quantity via contact water meterIndicator quantities: 100 und 500 ml bottlesTestomat® EVO TH CAL is supplied without mains switch. This is done to comply with the safety standard DIN EN 61010-1 for measuring, control and laboratory instruments. Of course, an external mains switch is available for purchase by you as a customer. You can order it from us as a disconnector under article no. 850925, "external cam switch with protection class IP65".
The Testomat® LAB CL and the Testomat® LAB CL-R are robust, wet chemical online measuring converter to measure the concentration of total chlorine or free chlorine in the measuring range 0 - 5 mg/l. The instrument is suitable for controlling the water quality of water treatment plants, drinking water plants, process water monitoring and for monitoring the chlorine concentration in the cooling tower process.Instrument operation is based on the DPD method according to EN ISO 7393-2. The analysis is carried out through the addition of two reagents and the measurement result is obtained after a reaction time of approx. 60 seconds (pure measurement time without flush time).Please note that Testomat® LAB CL and Testomat® LAB CL-R are developed for use in multi-parameter concepts or for integration into an existing higher-level controlconcept.In addition to the 4-20 mA output for the transmission of the measured values, this series has an RS232 interface for the transmission of the measured values and error & status messages. Furthermore, all data are continuously recorded on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format in a structured way and can be used for detailed observations at any time.The Testomat® LAB CL and CL-R convinces with new functionalities:Execution of parameterization by SD card or the "Service Monitor" software via mini-USB (on the device side) to USB 2.0 (for example PC/notebook)Multilingual menu navigation software in German, English, French, Dutch, PortugueseFirmware update via SD card
compact design
optimized water detection based on an optical measuring method [#dspacer#][#dspacer#]optimized reagent set for total chlorine measurement (reduction from three to tow reagents for total chlorine)Integrated self-test with continuous monitoring
Automatic venting of the indicator line Tried and tested performance profile: High-precision peristaltic pumpsReliable and low-maintenance operation
Minimal reagent and water consumption
Analog output 4 - 20 mA for transmission of measured values
RS232 interface for transmission of measured values & fault messages
Common alarm output
Optimised reagents: Only 2 reagents for the determination of total chlorineOptimised reagent bottles: Filling quantities adjusted so that both bottles are used up at the same timeAdditional functions of the CL-R version: Parameterisation and readout of the unit parameters via the RS232 interfaceAnalysis triggering:Automatic interval operation (interval pause adjustable from 10-60 minutes)
Measuring phase mode (start impulse triggers a sequence of analyses for a period of 10 minutes to 12 hours)
External analysis input (start/stop)
Hand start